How do I calculate the metal shield cross-section of a medium-voltage single-core cable?

2 years ago 2151 0 News

1686554209641205.jpg


Calculation of Metal Shield Cross-Section for Medium Voltage Cables


Medium voltage cables are usually stranded by several or groups of wires into a rope-like cable, each group of wires is insulated from each other and often twisted around a center, and the entire outer shell is covered with a highly insulating covering.

Medium-voltage power cables are 35 kV and below power cables.

Medium-voltage power cables use a single-core structure, which helps to increase the cable's load capacity and enhance the system load.

It is also able to reduce the occurrence of phase-to-phase short circuits in the event of cable insulation faults, while also reducing the weight of a single cable and increasing the length of the loading tray, facilitating transportation and construction.

It greatly reduces the number of joints in the line and changes three-phase joints to single-phase joints, making joint sealing simpler and more reliable. However, the design is easy to ignore the correct selection and determination of the structure and cross-section of the metal shield of the medium voltage single-core power cable, resulting in the potential for serious operating accidents in the power system.


The Structure of the Metal Shield

The metal shield is an important structure of medium-voltage power cable, in normal operation the cable will pass capacitive current, short circuit, and as a short-circuit current path.

At the same time, the electromagnetic field output when the cable is energized and shielded in the insulated core reduces electromagnetic interference to the outside world.

GB/T 12706-2008 standard for medium voltage power cable metal shielding structure form is specified, that is, by one or more metal tape, metal braid, a concentric layer of metal wire, or the combination of metal wire and metal tape structure, can also be a metal jacket or metal armor layer.

Copper tape shielding consists of a layer of overlapping wrapped soft copper tape, but also can use a double layer of copper tape gap wrapping.

The nominal thickness of copper tape for single-core cable shielding is not less than 0.12mm.

Copper wire shielding consists of sparsely wrapped soft copper wire, the surface of which is wrapped with reverse copper wire or copper tape tied.

The average gap between adjacent copper wires should be no more than 4mm.


Metal Shielding Structure Process Characteristics

In the whole cable manufacturing process, the metal shielding process is not complicated, but it is in direct contact with the insulation core. Without attention to detail, it is easy to make the metal shielding lose function, and this will cause serious cable quality problems.

Copper Tape Wrapping Shielding Process Characteristics

Copper tape wrapping shielding is the traditional shielding process, but also in the form of single-layer overlap lap wrapping.

Power cable using this method has the advantages of a smaller outside diameter, lighter weight, and lower cost.

Requirements for the use of copper tape for annealed soft copper tape, the copper tape is not allowed to have broken, rolled edges, and other defects.

Wrapping to adjust the tension of the appropriate package tape and the closing tray to be padded with foam pearl cotton to avoid core lacerations.

Copper tape wrapping should be tight and flat, there should be no oxidation, curling, bulging, copper cracking, or wrinkling and revealing the phenomenon of a semi-conductive layer inside.

Copper tape joints are strictly prohibited to use tape lap or tin welding, must use electric welding, and lap length of not less than 20mm, welding should be flat and firm, and the joint should be sandpaper for flattening and polishing.

However, the soft copper tape used for shielding is mostly recycled copper, and its electrical properties are difficult to meet the requirements of GB/T 11091-2005 standard.

After the cable is put into operation in this way, the contact surface of the copper belt is easily oxidized.

And due to bending and hot and cold deformation of copper strip contact surface reduction, resulting in increased contact resistance, but also easy to make the copper strip arch embedded in the insulation shield layer and damage the core.

Copper Wire and Copper Tape Sparse Winding Shielding Process Characteristics

The copper wire and copper tape sparse winding shielding method can structurally improve the disadvantages of the copper tape wrapping shielding method.

It does not have the oxidation layer generated by the copper tape lap, nor strong bending and hot and cold deformation, the sparsely wound copper tape is less likely to arch embedded in the insulation shield.

However, the cable produced in this way has a larger outer diameter, heavier weight, and higher cost.

In particular, the sparsely wound copper wire is easy to strangle into the insulation shield in production and use, affecting the appearance of the insulation core. This causes an increase in partial discharge of the cable or even exceeds the standard, and can seriously cause the cable to break through.

To avoid damage to the insulation core of copper wire sparse winding, the design can be used in two ways:

① In the insulation core outside the wrapping 1 to 2 layers of thickness of about 0.2mm semi-conductive nylon tape.

② in the three-layer co-extrusion process increase the thickness of the insulation shield layer, the thickness from the usual 0.6mm to 1.0 ~ 1.2mm.


Metal Shield Cross-Section Determination

The cross-section of the metal shield directly affects the cable's ability to withstand short-circuit current during a fault.

If the cross-sectional area is too small, it will overheat or burn off when the short-circuit current passes through and damage the insulation.

Therefore, the cross-section of the metal shield needs to be determined according to the fault current capacity.

 

Differentiation between Low-Voltage and High-Voltage Cables

Identifying Low-Voltage Lines

Outdoor low-voltage lines have several distinct characteristics:

① Basically, they are supported by concrete poles, and the concrete poles are short, generally not exceeding 5 meters.

② the same thickness of the wire, and the number of multiples of 4, which is because the low-voltage wire generally uses a three-phase four-wire system. If these characteristics can determine the line voltage of the wire is 380 volts, the phase voltage of 220 volts.

Identify high-voltage lines

High-Voltage Lines also have Obvious Characteristics

① If the wire thickness is the same, the number of multiples of 3, this is because the transmission line is generally three-phase transmission, and these characteristics can determine the wire for 10,000 volts.

② If the wire thickness is not the same, the number of thick lines is a multiple of 3, the fine line is only 2, and the assumption is that the highest in the.

This is because the thin line is not used for power transmission, but for lightning protection, also called lightning line.

If these characteristics are available then the wire can be identified as a high-voltage line.

Further Identification of High-Voltage Lines

To improve transmission capacity, high-voltage lines generally use split wires.

In layman's terms is the original one phase of a line, now with several wire bundles in place of the original one line.

Knowing this will be easy to identify the voltage level of the wire.

①One phase of a wire is 110,000 volts.

②One-phase two-wire is 220,000 volts.

③One phase of four lines is 500,000 volts.

 

Now many tenders require cable companies to design the shielding structure and determine the shielding cross-section according to the laying conditions and short-circuit current.

Therefore, the design of medium-voltage single-core power cable should fully consider the ability of the metal shield to carry short-circuit current, through the calculation and selection, to provide users with qualified and assured products.

INQUIRY
主站蜘蛛池模板: 铠甲勇士第一部52集全 | 精品国产3级a | 久久成年片色大黄全免费网站 | 亚洲一区二区三区久久久 | 三级黄色性生活视频 | 在线观看韩国av | 自拍偷拍在线视频 | 性色av一区二区三区 | 久久人人爽人人爽 | 色呦呦网站入口 | 好吊日好吊操在线 | 在线观看热码亚洲av每日更新 | 7777精品伊久久久大香线蕉 | 精品久久久久久无码人妻蜜桃 | 亚洲精品免费看 | 亚洲成人av一区二区三区 | 黄色网站小视频 | 亚洲视频一区二 | 中文字幕第三区 | 免费看裸体美女脱了衣服露视频胸 | 天天槽夜夜槽槽不停 | 一个人看的免费视频WWW中文字幕 | AAAA级少妇高潮大片在线观看 | 日韩中文字幕组 | 亚洲另类春色 | 黑人巨大无码中文字幕无码 | 欧美人成片免费看视频 | 久久久www成人免费无遮挡大片 | 97欧美一乱一性一交一视频 | 视频二区一区 | 天天艹av| 成人性视频免费网站在线 | 久草超碰| 精品中文字幕在线2019 | 在线观看片免费人成视频播放 | 欧美不卡三区 | 亚洲AV人无码综合在线观看 | 四虎最新紧急入口 | 少妇被猛烈进入A片 | 日本无码一区二区三区在线观看 | 国产高清视频一区二区在线观看 |