女人张开腿让男桶喷水高潮_国内精品免费一区二区2001_日韩综合在线播放_麻豆在网站1区_欧美日韩在线视频首页_天天狠天天天天透在线

sales@zmscable.com

What are the main methods of power cable withstand voltage test?

2 years ago 2082 0 News


The main methods of power cable withstand voltage test


A cable withstand voltage test is a way to find faults in the presence of cables. It is easily affected by various factors during the test, resulting in problems such as failure and short circuits. 

The main methods of several cables to withstand voltage tests are described below.

First, ultra-low frequency withstand voltage test

1562638173494213.png

The ultra-low frequency (0.1Hz) withstand voltage test method first appeared in 1980, and it is mainly a non-destructive test method for observing whether there is an insulation defect in cable operation, and the method has been verified by a large number of laboratory tests and field tests. 

The low-frequency withstand voltage test has a good application effect in the low-voltage power cable withstand voltage test. 

The method utilizes the principle of converting 50 Hz alternating current into direct current voltage through rectification and filtering, and then converting the direct current voltage into an alternating current voltage of 1 kHz through an inverter circuit, and then performing amplitude modulation processing by a 0.1 Hz sinusoidal oscillator, and after amplitude modulation, 1 kHz. 

The amplitude wave such as the AC voltage is converted into a 0.1 Hz varying beam wave. 

It is mainly based on the high voltage formed between the high voltage transformer and the voltage multiplying circuit, which is mainly characterized by a sine wave and is mediated by a varistor so that the high AC voltage load output is a 0.1 Hz high voltage sinusoidal waveform. 

The advantages of the ultra-low frequency withstand voltage test are mainly: 1 no damage; 2 high accuracies; 3 small sizes, easy to carry. However, the output voltage level of this method is low, and it is mainly used in the medium and low voltage cable withstand voltage test.

Second, the modulated power frequency series resonance test

The method mainly utilizes the inductive reactance of the reactor and the capacitive reactance of the measured cable capacitance to generate a resonance in a 50 Hz power frequency environment, and a high voltage is generated in the process. The advantages of the modulated power frequency series resonance test are: 

1 The output current waveform is basically a sine wave.

2 Is high in specificity, and only after the series resonant circuit satisfies the condition for generating resonance, a high voltage is formed, and the cable to be tested is once tested. 

If there is a problem, it will cause a loop abnormality, which is equivalent to a short circuit of the cable. 

The high voltage will also appear to be uniformly dropped. 

Moreover, since the reactor can limit the short-circuit current, the protection device is not affected, and thus it is not necessary to install a resistor protection device. 

The disadvantage of this test method is that the operation is complicated, the system quality factor is not high, the automation level is low, and the noise is large, which limits its application in practice.

1562638215827306.png

Third, the frequency conversion series resonance test

The principle of frequency conversion series resonance test is similar to the above-mentioned principle of modulated power frequency series resonance test. 

The difference is that the frequency conversion series resonance test realizes the resonance of the test circuit by adjusting the output voltage frequency in the variable frequency power supply.

In the frequency series resonance test, the resonance of the test circuit is realized by the inductance generated by the regulating reactor at the 50 Hz power frequency. 

The advantage of the variable frequency series resonance test is that when the required power supply capacity of the test is lower than the power supply capacity of the cable under test, the test can be performed at much lower power than the required power supply, which can effectively improve the efficiency of the field test and can overcome.

The shortcomings of the modulated power frequency withstand voltage test device make it more widely used in real life. 

In addition, the operating frequency of the variable frequency series resonance test is only 30 to 300 Hz, which can improve the problem that the frequency of the ultra-low frequency withstands voltage test is too low and the loss is small, which is inconsistent with the actual loss. 

Therefore, the results obtained by the variable frequency series resonance withstand voltage test are precise, comprehensive, and reliable.


@ZMSCABLE MANUFACTURER


Tags:
Power Cable
INQUIRY
主站蜘蛛池模板: 久久久久久久国产免费看 | 亚洲国产精品女人久久久 | 国产玉足榨精视频在线 | 国产精品中文 | 欧美婷婷六月丁香综合色 | 伊人久久视频 | 91制片厂色版在线观看 | 夜夜操天天操 | 最近中文国语字幕在线播放视频 | 黄色av免费在线 | 视频免费1区二区三区 | 免费费很色视频大片 | 亚洲中文字幕VA福利 | 中文字幕无码精品亚洲资源网久久 | 人人人爽人人爽人人AV| 国产精品网在线观看 | 亚洲精品无码AV专区最新 | 国产综合视频在线观看 | 日韩天码 | 亚洲区久久 | 国产乱人伦在线播放 | 成人18视频日本 | 久久午夜精品影院一区 | 天天爽影院一区二区在线影院 | 黄色片一级免费看 | 黑人chinese中国china国产 | 亚洲免费视频一区 | 天天骑天天干 | 国产呦精品一区二区三区网站 | 亚色网址 | 蜜桃精品成人影片 | 亚洲伦理在线视频 | 欧美成欧美va | 性欧美8处一14处破 欧美三级不卡在线播放 | youjizz中国少妇| 日韩一区二区久久久 | 黄色va视频 | 香蕉免费一区二区三区 | 办公室少妇激情呻吟a片在线观看 | 69xx免费视频 | 香蕉久久人人爽人人爽人人片av |